Table of Contents Table of Contents
Previous Page  316 / 528 Next Page
Information
Show Menu
Previous Page 316 / 528 Next Page
Page Background

Enclosed Motor Controls

Enclosed Motor

Controls

A-312

Data subject to change without notice.

www.weg.net

Enclosed Starters

WEG’s full voltage non-reversing combination starters represent a competitive alternative to the traditional NEMA

starters by offering:

Reduced overall dimensions, yet providing reasonable internal wiring space

Rotary through-the-door disconnect instead of the traditional flange operator

UL/CSA approved performance in more compact components.

Two series are available off the shelf:

MCCB disconnect – ESWC Series

Motor protector – ESWE & ESWF Series

Combination Starter Basics

Combination starters are the most common

type of packaged motor controllers. They are

called combination because of their construction

and combined functions required by the US

National Electric Code (NEC): Motor Disconnect,

Motor Branch Circuit Protection, Motor

Controller and Motor Overload Protection. UL &

CSA currently recognizes six different

constructions of combination starters that meet

the requirements of a motor branch circuit.

Constructions Types A through D are traditional

starters that use either a listed disconnect

switch and fuses or a listed circuit breaker as

the disconnect means and for short circuit

protection. Each type uses a separate UL508

listed motor controller and overload relay.

Recently revisions on UL508 introduced the

Type E and Type F starters.

Type E starter is a self-protected combination motor controller

that combines in a single device all the required functions of a

combination starter eliminating any additional requirements for

upstream fuses or circuit breaker. Type F starter consists of a

listed manual Type E combined with a UL508 listed contactor.

UL

Combination

Starter Type

Device Used for Component Function

Disconnected

Branch Circuit

Protection

Motor Controller

Motor OL Relay

A

UL 98 Manual

Disconnect

UL 248 Fuses

UL 508 Magnetic

or Solid State

Controller

UL 508 Motor

Overload Relay

B

UL 508 Motor

Short Circuit

Protector

C

UL 489 Inverse Time Circuit

Breaker

D

UL 489 Instantaneous Trip

Circuit Breaker

E

UL 508 Self-Protected Combination Controller

F

UL 508 Manual Self-Protected

Combination Controller

UL 508 Magnetic

or Solid State

Controller

UL 508 Manual

Self-Protected

Combination

Controller

Enclosed Motor

Controls